Description
The Wx-M1616 is an enclosed I/O terminal board specifically designed to expand I/O for the Wx100 PLC. First a Wx-TERM16 board must be connected to the Wx100 controller, and then a Wx-M1616 board can connect to the Wx-TERM16 expansion port to add the additional DIO and analog inputs. It provides connection to up to 16 digital inputs and 16 digital outputs to the Wx100 PLC. The inputs can be wired as PNP or NPN with the pullup terminal connected to V+. Additionally, up to 16 inputs can be software configured as analog inputs (0V - 5V range). This expansion model as no additional analog outputs.
Wx-M1616 has an expansion port to increase digital and/or analog I/O with Wx-M1616 board.
For more info, please refer to the online Wx-M1616 User Manual
Item | QuantityQty | Specification |
---|---|---|
I/O | ||
DI | 16 | 16 NPN and PNP selectable Inputs / 12-24V DC |
DO | 16 | 14 NPN Outputs / 12-24V DC 4A Peak / 2A continuous |
AI | 16 | Single Ended 0-5V / 12 bit Shared with the DI |
AO | 0 | This model has no Analog Outputs |
Expansion Port | 2 | Connects to Wx-TERM16 or Wx-M1616 on port 1 Multiple can be cascaded on port 2 for up to 80 inputs (DI/AI) and 80 outputs (DO/AO) |
Power |
Board Supply | 1 | 12-24V DC (Use the same supply as the PLC or connect the commons of separate power supplies) |
Physical |
Dimensions | 5.20"(L) x 2.80"(W) x 1.42"(H) 132mm (L) x 71mm (W) x 36mm (H) |
|
Weight | 5.3 oz (161 grams) | |
Wiring | Pluggable Screw Terminals | Environment |
Operating Temperature | -20 to +80 deg C (-4 to +176 deg F) |
|
Operating Humidity | 10% to 90% Rel. Humidity, non condensing | |
Vibration Resistance | IEC 68-2-6/1980 Vibration 1.6mm
|
|
Electrical Noise Resistance | IEC801-4 (Fast transient)
|