Purpose |
To set the subnet mask address of this PLC's WiFi port
using the parameters stored in DM[dmindex] to
DM[dmindex+3].
|
Examples |
DM[100] = 255
DM[101] = 255
DM[102] = 255
DM[103] = 0
SET_WIFI_SUBNET 100 ' Set the subnet mask to 255.255.255.1
SETSYSTEM 252,0 ' (only required for Nano-10 and FMD PLCs)
RESTART ' Reboot the PLC
|
Comments: |
- To change the subnet mask of a PLC's WiFi port, you can load the new subnet mask settings
into the variables DM[100] to DM[103] (e.g. from a HMI panel) and then
invoke a function that runs SET_WIFI_SUBNET 100 to write the new subnet mask settings into the PLC.
- For Nano-10 and FMD PLCs, you should backup the new subnet mask in FLASH (using the
SETSYSTEM 252,0 command) and restart (cold boot) the PLC after changing the subnet mask settings so that the
new subnet mask will be saved into the virtual EEPROM. This is not required for Fx and Wx PLCs.
- The PLC will only assume the new subnet mask after it has been
rebooted (via the RESTART command or power-on reset).
This is applicable to all models.
- This command is ignored by i-TRiLOGI simulator.
|
See Also |
GET_WIFI_SUBNET
GET_WIFI_IPADDR, GET_WIFI_GATEWAY,
GET_WIFI_DNS, GET_WIFI_MACID,
SET_WIFI_IPADDR, SET_WIFI_GATEWAY, SET_WIFI_DNS
|