Purpose |
To set the DNS address of this PLC's WiFi port
using the parameters stored in DM[dmindex] to
DM[dmindex+3].
|
Examples |
DM[100] = 192
DM[101] = 168
DM[102] = 0
DM[103] = 1
SET_WIFI_DNS 100 ' Set the DNS address to 192.168.0.1
SETSYSTEM 252,0 ' (only required for Nano-10 and FMD PLCs)
RESTART ' Reboot the PLC
|
Comments: |
- To change the DNS address of a PLC's WiFi port, you can load the new DNS address
into the variables DM[100] to DM[103] (e.g. from a HMI panel) and then
invoke a function that runs SET_WIFI_DNS 100 to write the new DNS address into the PLC.
- For Nano-10 and FMD PLCs, you should backup the new DNS in FLASH (using the
SETSYSTEM 252,0 command) and restart (cold boot) the PLC after changing the DNS address so that the
new DNS address will be saved into the virtual EEPROM. This is not required for Fx and Wx PLCs.
- The PLC will only assume the new DNS address after it has been
rebooted (via the RESTART command or power-on reset).
This is applicable to all models.
- This command is ignored by i-TRiLOGI simulator.
|
See Also |
GET_WIFI_DNS
GET_WIFI_IPADDR, GET_WIFI_SUBNET,
GET_WIFI_GATEWAY, GET_WIFI_MACID,
SET_WIFI_IPADDR, SET_WIFI_GATEWAY,
SET_WIFI_SUBNET
|