Technical support / Re: MBTCP Time-out was 0 , what does it do
« Last post by support on November 15, 2022, 06:50:13 PM »
If the MBTCP time-out is set to zero then the firmware will automatically adjust the MBTCP server time-out to 20 seconds.

Note that this time-out is for the PLC acting as slave (Server) to an external Modbus TCP master (client). 

Did you try to run "PRINT #4 "<TCPCONNECT xxxx>"? Note that TCPCONNECT is for the PLC to act as a client to access an external TCP server. It is not to be used to configure the PLC as a Modbus TCP server.

I checked the Moxa 5230 - it appears to be a MODBUS TCP-to-MODBUS RTU gateway converter? If you want to access the serial port on the Fx1616-BA PLC from an external Mobdus TCP master then MOXA 5230 can be used but you must configure the serial port on the MOXA to be compatible to that on the PLC. I don't understand why do you want to do that since you can already directly access the PLC via its Ethernet port...
82
Technical support / MBTCP Time-out was 0 , what does it do
« Last post by graham.burgess@stfc.ac.uk on November 14, 2022, 10:06:53 AM »
I have an HMI connected to a FX1616-Ba  using modbus over ethernet, I am also trying to add an extra serial port by doing a TCPconnect to a moxa 5230, when I connect (tcpconnect) to the moxa, the hmi complains about a lack of connection. increasing this value from 0 to 2 improves it greatly but not eliminates the problem. what happens if I take this value even higher?
many thanks
Graham
 
83
There isn't a Special Clock Pulse bit with a period of 2 seconds.

But there is a 1 second period clock named "Clk:1.0s.

You can use a COUNTER to generate a 2 second clock from Clk:1.0s

The trick is to make the COUTNER count up with the use of special function coil, [UpCntr].

A COUNTER with a set value of 1 will count 0,1,0,1... as an up-counter. The contact for the COUTNER will be active on the "0" count time period.

I have attached a screen shot of of the ladder logic to get this to happen.

Good luck,
   
Gary Dickinson
84
Technical support / How to send Clock Pulse of 2s using the Special Clock Pulse bit
« Last post by suhelens on November 10, 2022, 11:22:45 PM »
Hi! A bit new to TriPLC. This may be a simple question but how do I trigger a coil every 2s using the Special bit Clock pulse?
85
Technical support / Re: PLC INPUT Interrupt Behavior
« Last post by Lorne Van Dusen on November 08, 2022, 07:01:28 AM »
Gary I had had a similar issue and when I did some detailed testing I discovered that there was a 24VDC relay that was connected to a PLC output and the manufacture of the equipment forgot to install a diode across the coil. Be-leave it or not that spike created cause the PLC to call my interrupt that I used to reset the HSC value. 
I found out with some help from tech support that within the interrupt I could disable the interrupt then I could do a quick Refresh and read the input that was tied to the interrupt which now is at level logic then reset my HSC value then re-enable the interrupt . All this added less than 1ms which actually prevented the spike from resetting the HSC and was still more than fast enough to reset the HSC value instantly. 
86
Technical support / Re: PLC INPUT Interrupt Behavior
« Last post by garysdickinson on November 07, 2022, 01:34:35 PM »
Lorne,

I think your approach is reasonable. 

The feedback that I got from TRI is that the behaviors vary by PLC family. 

1. The Wx100 is based on a very different processor and the state of the physical INPUTs may continued to be visible to ladder logic while being used as an interrupt source. This is not the case with Fx based PLCs or the older FMD based PLCs.

2. There is some sort of debounce logic on INPUTs to filter out bounces that show up with mechanical contacts.  This mechanism is turned off for those INPUTs that are being used as INPUTs on some PLC  families.  The debounce mechanism is be based on ladder logic scan boundaries and may require more than a single scan to get settled.

The bottom line is that it can take one or more full scans of the ladder logic on most PLC families from when an INPUT interrupt is disabled until that INPUT's true state is visible to ladder logic.

Thanks for helping me think through this stuff.

Gary d





87
Technical support / Re: PLC INPUT Interrupt Behavior
« Last post by Lorne Van Dusen on November 03, 2022, 12:58:40 PM »
Gary
I think you have the right idea but you are over doing it.
Leave the Interrupt as a Rising Edge trigger then in the first line of the function disable the interrupt then do a REFRESH of the IO then do a TESTBIT of the input you want then you can set any relay you want or reset any counters etc.
Then before you exit turn the interrupt back on.
Then in your ladder logic you can reset the relay you set in the function any way you want
88
Frequently Asked Questions / Re: can we send sms?
« Last post by Sandy76 on October 31, 2022, 06:55:12 PM »
If your mobile phone can be connected to a PC HyperTerminal to send and receive text string as well as respond to AT command then you can use the TBASIC language to talk to your mobile phone. Hope it helps. 

Dumpster Rental Cedar City

89
General Discussions / Re: HSC in cusfn
« Last post by BetterBath on October 27, 2022, 06:25:04 AM »
I learned a little c++, so this topic seemed a bit familiar to me. Thank you for sharing.
Junk removalPet sitting Port St Lucie, FlPressurewashingpowerroofinghandyman
Pages: 1 ... 7 8 [9] 10